刘海燕,马建军,张惠.大型气候环境实验室空 气处理系统方案探讨[J].装备环境工程,2014,11(5):107-113. LIU Hai-yan,MA Jian-jun,ZHANG Hui.Discussion on Design of the Air Handing System in Large Climatic Environmental Test Laboratory[J].Equipment Environmental Engineering,2014,11(5):107-113.
大型气候环境实验室空 气处理系统方案探讨
Discussion on Design of the Air Handing System in Large Climatic Environmental Test Laboratory
投稿时间:2014-08-24  修订日期:2014-09-04
DOI:10. 7643 /issn. 1672-9242. 2014. 05. 021
中文关键词:  气候环境实验室  空气处理  循环风系统  新风系统  空气补偿系统
英文关键词:climatic environmental test laboratory  air handling  air cycling system  fresh air system  air compensation system
基金项目:
作者单位
刘海燕 中国飞机强度研究所, 西安 710065 
马建军 中国飞机强度研究所, 西安 710065 
张惠 中国飞机强度研究所, 西安 710065 
AuthorInstitution
LIU Hai-yan Aircraft Strength Research Institute of China, Xi忆an 710065, China 
MA Jian-jun Aircraft Strength Research Institute of China, Xi忆an 710065, China 
ZHANG Hui Aircraft Strength Research Institute of China, Xi忆an 710065, China 
摘要点击次数:
全文下载次数:
中文摘要:
      目 的 探讨适用 于大型气候环境实验室的空气处理系统方案。 方法 从大型气候环境实验室空气处理系统的功能出 发, 探讨循环风系统、新风系 统和空气补偿系 统方案, 并对各系 统的 工作流程和优劣进行分析, 在此基础上提出 优化的集成空气处理系 统方案。 结果 循环风系 统采用串 联风道比并联风道能更好地保证极限温湿度指标和均 匀 性指标, 循环风系 统与 空气补偿系 统集成方案优于两个个独立系统方案、具备可行性。 结论 该空气处理系 统方案适用 于大型气候环境实验室。
英文摘要:
      Objective To investigate the scheme of the air handling system which is suitable for the large climatic environmental test facility. Methods The scheme of the air cycling system, the fresh air system and the air compensation system was discussed based on the functions of the air handling system in large climatic environmental test laboratory. The working process as well as the advantages and disadvantages of each system were analyzed. An optimized integrated air handling system scheme was put forward based on the analysis. Results The air cycling system adopting the ducts in series could better ensure the limit temperature and humidity as well as the uniformity indices of the facility. The integration of the air cycling system with the air compensation system was better than the two independent systems, and was feasible. Conclusion The scheme of the air handling system put forward in this paper was suitable for the large climatic environmental facility.
查看全文  查看/发表评论  下载PDF阅读器
关闭

关于我们 | 联系我们 | 投诉建议 | 隐私保护 | 用户协议

您是第12768355位访问者    渝ICP备15012534号-5

版权所有:《装备环境工程》编辑部 2014 All Rights Reserved

邮编:400039     电话:023-68792835    Email: zbhjgc@163.com

视频号 公众号