Defrost of Heat Exchangers Using Secondary Refrigerant
Received:May 07, 2018  Revised:July 25, 2018
View Full Text  View/Add Comment  Download reader
DOI:10.7643/ issn.1672-9242.2018.07.011
KeyWord:climatic environmental test chamber  secondary refrigerant  frost-heat exchanger  multiple fin pitch  defrost
     
AuthorInstitution
MA Jian-jun Aircraft Strength Research Institute of China, Xi'an , China
LIU Hai-yan Aircraft Strength Research Institute of China, Xi'an , China
Hits:
Download times:
Abstract:
      Objective To solve the frost problem of heat exchangers used in extreme low temperature climatic test chamber with liquid secondary refrigerant as coolant to obtain feasible design scheme for defrost. Methods Based on the aspects of restrain-frost and defrost, two defrost systems including variable fin spacing frost-heat exchanger were designed and studied by experiment. Results The windward side of the variable fin spacing frost-heat exchanger frosted heavily while the leeward frosted lightly. Defrost time consumed by inner-defrost system was 3.5min while out-defrost system needs 7min. In combination with replacement of refresh air, water retained on the surface of frost-heat exchanger could be removed in 20min by flowing heat after inner-frost. Conclusion The variable fin spacing frost-heat exchanger can pre-dehumidify the air and protect the main heat exchanger. The inner-defrost system with good inner defrosting effect supported by fresh air purging and with steam as the heat source is successfully applied in large climatic environmental test laboratory.